Technical Specifications
MODEL FHV-30KW-ET
MAXIMUM PV INPUT POWER 40000 W
RATED    OUTPUT    POWER 30000 W
MAXIMUM     CHARGING     POWER 30000 W
Grid-Tie Operation
PV Input(DC)
Nominal DC Voltage /Maximum DC Voltage 720 VDC/1000 VDC
Start-up Voltage /Initial Feeding Voltage 320 VDC/350 VDC
MPP Voltage Range 350 VDC~900 VDC
Number of MPP Trackers /Maximum Input Current 3/A:26A,B:26A,C:26A
Number of Strings Per MPP Tracker A:2,B:2,C:2
Grid/Iutility Output(AC)
Nominal Output Voltage 230 VAC (P-N)/400 VAC (P-P
Output Voltage Range 184-265 VAC per phase
Nominal Output Current 43.5 Aper phase
Power Factor 0.9 lag to 0.9 lead
 Efficiency
Maximum Conversion Efficiency (DC/AC) 96.5%
European Efficiency@Vnominal 96%
Off-Grid Operation
AC Input
AC Start-up Voltage /Auto Restart Voltage 120-140 VAC/180 VAC per phase
Acceptable Input Voltage Range 170-280 VAC per phase
Maximum AC Input Curren 50 A
PV Input(DC)
Maximum DC Voltage 1000 VDC
MPP Voltage Range 350 VDC~900 VDC
Number of MPP Trackers /Maximum Input Current 3/A:26A,B:26A,C:26A
Battery Mode Output(AC)
Nominal Output Voltage 230 VAC (P-N)1400 VAC (P-P)
Output Waveform Pure sine wave
Eficiency (DC to AC) 97%
Hybrid Operation
PV Input(DC)
Maximum DC Voltage 1000 VDC
Start-up Voltage IInitial Feeding Voltage 320 VDC/350 VDC
MPP Voltage Rang 350 VDC~900 VDC
Number of MPP Trackers /Maximum Input Current 31A:26A,B:26A,C:26A
Grid Output(AC)
Nominal Output Voltage 230 VAC(P-N)/400 VAC(P-P'
Output Voltage Range 184-265 VAC per phase
Nominal Output Current 43.5 Aper phase
AC Input
AC Start-up Voltage /Auto Restart Voltage 120-140 VAC /180 VAC per phase
Acceptable Input Voltage Range 170-280 VAC per phase
Maximum AC Input Current 50 A
Battery Mode Output(AC)
Nominal Output Voltage 230 VAC (P-N)1400 VAC (P-P)
Efficiency (DC to AC) 97%
Battery&Charger
Battery Voltage Range 500~900 VDC
Maximum Charging Current 50A
General
Physical
Dimension,DxWxH(mm) 255x660x750
Net Weight (kgs 73
Interace
Communication Port RS-232,USB,DRY CONTACT,RS-485 and Wi-Fi
Intelligent Slot Optional SNMP,MODBUS and GPRS
Environment
Humidity 0~100%RH
Operating Temperature -25°℃ to 60℃(>45°℃ De-rating)
Altitude 0~1000 m**